Recommendation
Current position:Home > Input Reactor > Input Reactor
Circuitry application:
At the input side of Six pulse rectifier equipment(inverter、parker、the input side of the integrated rectifier cabinet at electric vehicle charging stations), it can help to ameliorate the power factor, inhibit the impact current, also protect the Grid from being interfered by the harmonic wave caused by the inverter.
Performance features:
Rated voltage |
3-AC400V/AC690V/AC1140V ,50HZ |
Insulation grade |
F/H |
Noise |
≤70 dB |
Electric strength |
AC3000V/AC4200V 50Hz 5s leakage current≤5m A |
Ambient temperature |
-25℃~55℃/(75℃,explosion-proof ) |
Operative norm |
GB10229-88 reactor、IEC289:1987 reactor、JB9644-1999 reactor for transmission semiconductor |
Solutions for the input side of the inverter:
Dimensions and technical parameter:
Technical parameter of input reactor(UD=2%):
System voltage: 3-AC400V, 50HZ, Insulation level: F
Specifications and models
Figure No.
Power of 6 pluse rectifier(KW)
Rated current(A)
Inductance (mH)
Weight (KG)
Dimensions(mm)
W
D
H
W0
D0
A*B
SACL-0005-EISC-280B
A
2.2
5
2.8
1.5
93
69
110
40
48
7*11
SACL-0010-EISC-140B
3.7
10
1.4
2.6
115
73
125
50
53
7*11
SACL-0013-EISC-108B
5.5
13
1.08
2.8
115
73
125
50
53
7*11
SACL-0016-EISC-876C
7.5
16
0.876
2.9
115
73
125
50
53
7*11
SACL-0025-EISC-560C
B
11
25
0.56
5.3
150
95
160
60
67
7*11
SACL-0030-EISC-467C
15
30
0.467
5.6
150
95
160
60
67
7*11
SACL-0040-EISA-350C
C
18.5
40
0.35
5.7
180
110
160
80
67
7*11
SACL-0045-EISA-310C
22
45
0.31
5.8
180
110
160
80
67
7*11
SACL-0060-EISA-234C
30
60
0.234
8.5
180
130
160
80
87
7*11
SACL-0075-EISA-187C
37
75
0.187
8.9
180
130
160
80
87
7*11
SACL-0090-EISA-155C
45
90
0.155
9.2
180
130
160
80
87
7*11
SACL-0110-EISA-128C
55
110
0.128
14.5
230
160
220
110
85
9*18
SACL-0150-EISA-934D
75
150
0.0934
15.2
230
160
220
110
85
9*18
SACL-0180-EISA-780D
90
180
0.078
19.5
230
175
220
110
100
9*18
SACL-0220-EISA-640D
110
220
0.064
20.8
230
175
220
110
100
9*18
SACL-0260-EISA-540D
D
132
260
0.054
27.6
260
185
265
140
110
9*18
SACL-0320-EISA-440D
160
320
0.044
29.2
260
185
265
140
110
9*18
SACL-0400-EISA-350D
200
400
0.035
35.4
300
205
280
170
110
11*18
SACL-0480-EISA-290D
250
480
0.029
47.3
300
230
280
170
135
11*18
SACL-0540-EISA-260D
280
540
0.026
48.7
300
230
280
170
135
11*18
SACL-0600-EISA-234D
315
600
0.0234
50.1
300
230
280
170
135
11*18
SACL-0800-EISA-175D
400
800
0.0175
69.1
360
255
375
190
135
13*26
SACL-1000-EISA-140D
500
1000
0.014
74.8
360
255
375
190
135
13*26
SACL-1100-EISA-127D
E
560
1100
0.0127
98
430
305
410
240
175
14*28
SACL-1200-EISA-117D
630
1200
0.0117
100
430
305
410
240
175
14*28
System voltage: 3-AC690V, 50HZ, Insulation level: F
Specifications and models
Figure No.
Power of 6 pluse rectifier(KW)
Rated current(A)
Inductance (mH)
Weight (KG)
Dimensions(mm)
W
D
H
W0
D0
A*B
SACL-0020-EISC-128B
B
15
20
1.28
5.5
150
95
160
60
67
7*11
SACL-0030-EISC-850C
22
30
0.85
8.7
180
130
190
80
87
7*11
SACL-0045-EISA-565C
C
37
45
0.565
12.7
230
160
190
110
85
9*18
SACL-0060-EISA-425C
45
60
0.425
14.7
230
160
220
110
85
9*18
SACL-0090-EISA-282C
75
90
0.282
16.3
230
160
220
110
85
9*18
SACL-0110-EISA-230C
90
110
0.23
20.4
230
175
220
110
100
9*18
SACL-0150-EISA-170C
110
150
0.17
21.5
230
175
220
110
100
9*18
SACL-0200-EISA-128C
D
160
200
0.128
29.1
260
185
265
140
110
9*18
SACL-0250-EISA-102C
200
250
0.102
32.1
260
185
265
140
110
9*18
SACL-0300-EISA-850D
250
300
0.085
37.8
300
200
280
170
110
11*18
SACL-0400-EISA-640D
355
400
0.064
52.2
300
225
280
170
135
11*18
SACL-0480-EISA-530D
450
480
0.053
70.1
360
250
375
190
135
13*26
SACL-0600-EISA-425D
560
600
0.0425
74.7
360
250
375
190
135
13*26
SACL-0800-EISA-320D
E
710
800
0.032
100.5
430
290
410
240
175
14*28
SACL-1000-EISA-254D
900
1000
0.0254
107.1
430
290
410
240
175
14*28
SACL-1100-EISA-230D
1000
1100
0.023
139.1
430
310
520
240
190
14*28
SACL-1400-EISA-180D
1200
1400
0.018
152.3
430
310
520
240
190
14*28
System voltage: 3-AC690V, 50HZ, double-quadrant explosion-proof series frequency converter, Insulation level: H; Ceiling of reactor temperature rise≤70K-80K
Specifications and models
Figure No.
Power of 6 pluse rectifier(KW)
Rated current(A)
Inductance (mH)
Weight (KG)
Dimensions(mm)
W
D
H
W0
D0
A*B
FACL-0090-EISC-282C
C
75
90
0.282
17.9
230
160
220
110
85
9*18
FACL-0110-EISC-230C
90
110
0.230
21.3
230
175
220
110
100
9*18
FACL-0150-EISC-170C
110
150
0.17
24.2
230
175
220
110
100
9*18
FACL-0200-EISC-128C
D
160
200
0.128
31.6
260
185
265
140
110
9*18
FACL-0250-EISC-102C
200
250
0.102
35.0
260
185
265
140
110
9*18
FACL-0300-EISC-850D
250
300
0.085
42.8
300
200
280
170
110
11*18
FACL-0400-EISC-640D
355
400
0.064
56.1
300
225
280
170
135
11*18
FACL-0480-EISC-530D
450
480
0.053
73.6
360
250
375
190
135
13*26
FACL-0600-EISC-425D
560
600
0.0425
80.6
360
250
375
190
135
13*26
FACL-0800-EISC-320D
E
710
800
0.032
105.7
430
285
410
240
175
14*28
FACL-1000-EISC-254D
900
1000
0.0254
116.4
430
285
410
240
175
14*28
FACL-1100-EISC-230D
1000
1100
0.023
146.6
430
300
510
240
190
14*28
FACL-1400-EISC-180D
1200
1400
0.018
163.2
430
320
510
240
190
14*28
System voltage: 3-AC1140V, 50HZ, double-quadrant explosion-proof series frequency converter, Insulation level: H; Ceiling of reactor temperature rise≤70K-80K
Specifications and models
Figure No.
Power of 6 pluse rectifier(KW)
Rated current(A)
Inductance (mH)
Weight (KG)
Dimensions(mm)
W
D
H
W0
D0
A*B
FACL-0110-EISC-380C
D
160
110
0.38
30.9
260
185
265
140
110
9*18
FACL-0150-EISC-280C
200
150
0.28
34.7
260
185
265
140
110
9*18
FACL-0200-EISC-210C
280
200
0.21
44.0
300
200
280
170
110
11*18
FACL-0250-EISC-168C
355
250
0.168
58.0
300
205
280
170
135
11*18
FACL-0300-EISC-140C
450
300
0.14
73.4
360
210
375
190
135
13*26
FACL-0350-EISC-120C
500
350
0.12
78.8
360
220
375
190
135
13*26
FACL-0400-EISC-105C
630
400
0.105
87.4
360
250
375
190
135
13*26
FACL-0480-EISC-875D
E
710
480
0.0875
108.6
430
275
410
240
175
14*28
FACL-0600-EISC-700D
900
600
0.07
123.6
430
275
410
240
175
14*28
FACL-0700-EISC-600D
1000
700
0.06
139.3
430
290
510
240
190
14*28
FACL-0800-EISC-525D
1200
800
0.0525
147.0
430
290
510
240
190
14*28
Remarks:Copper DC reactor(type EISC) will be a little heavier, the remaining items are the same, A/B/C stand for three-phase input side;X/Y/Z stand for output side.
Technical parameter of input reactor(UD=4%)
System voltage: 3-AC400V,50HZ, Insulation level: F
Specifications and models
Figure No.
Power of 6 pluse rectifier(KW)
Rated current(A)
Inductance (mH)
Weight (KG)
Dimensions(mm)
W
D
H
W0
D0
A*B
SACL-0005-EISC-560B
A
2.2
5
5.6
2.7
115
73
125
50
53
7*11
SACL-0010-EISC-280B
B
3.7
10
2.8
5.1
150
95
160
60
67
7*11
SACL-0013-EISC-216B
5.5
13
2.16
5.6
150
95
160
60
67
7*11
SACL-0016-EISC-175B
7.5
16
1.75
5.6
150
95
160
60
67
7*11
SACL-0025-EISC-112B
11
25
1.12
8.4
180
130
190
80
87
7*11
SACL-0030-EISC-934C
15
30
0.934
8.7
180
130
190
80
87
7*11
SACL-0040-EISA-700C
C
18.5
40
0.7
12.6
230
160
190
110
85
9*18
SACL-0045-EISA-622C
22
45
0.622
12.8
230
160
190
110
85
9*18
SACL-0060-EISA-467C
30
60
0.467
14.8
230
160
220
110
85
9*18
SACL-0075-EISA-374C
37
75
0.374
15.8
230
160
220
110
85
9*18
SACL-0090-EISA-312C
45
90
0.312
16.5
230
160
220
110
85
9*18
SACL-0110-EISA-255C
55
110
0.255
20.6
230
175
220
110
100
9*18
SACL-0150-EISA-187C
75
150
0.187
21.9
230
175
220
110
100
9*18
SACL-0180-EISA-156C
D
90
180
0.156
29.6
260
185
265
140
110
9*18
SACL-0220-EISA-128C
110
220
0.128
32.1
260
185
265
140
110
9*18
SACL-0260-EISA-108C
132
260
0.108
38.1
300
195
280
170
110
11*18
SACL-0320-EISA-875D
160
320
0.0875
39.4
300
195
280
170
110
11*18
SACL-0400-EISA-700D
200
400
0.07
50.8
300
225
280
170
135
11*18
SACL-0480-EISA-580D
250
480
0.058
70.1
360
250
375
190
135
13*26
SACL-0540-EISA-520D
280
540
0.052
71.2
360
250
375
190
135
13*26
SACL-0600-EISA-468D
315
600
0.0468
75.3
360
250
375
190
135
13*26
SACL-0800-EISA-350D
E
400
800
0.035
103.2
430
290
410
240
175
14*28
SACL-1000-EISA-280D
500
1000
0.028
114.8
430
290
410
240
175
14*28
SACL-1100-EISA-254D
560
1100
0.0254
138.5
430
305
510
240
190
14*28
SACL-1200-EISA-233D
630
1200
0.0233
145.5
430
305
510
240
190
14*28
System voltage: 3-AC690V,50HZ, Insulation level: F
Specifications and models
Figure No.
Power of 6 pluse rectifier(KW)
Rated current(A)
Inductance (mH)
Weight (KG)
Dimensions(mm)
W
D
H
W0
D0
A*B
SACL-0020-EISC-256B
B
15
20
2.56
8.7
180
130
190
80
87
7*11
SACL-0030-EISC-170B
22
30
1.7
9.8
180
130
190
80
87
7*11
SACL-0045-EISA-113B
C
37
45
1.13
19.3
230
175
220
110
100
9*18
SACL-0060-EISA-850C
45
60
0.85
20.3
230
175
220
110
100
9*18
SACL-0090-EISA-564C
D
75
90
0.564
27.7
260
185
265
140
110
9*18
SACL-0110-EISA-460C
90
110
0.46
30.4
260
185
265
140
110
9*18
SACL-0150-EISA-340C
110
150
0.34
37.3
300
190
280
170
110
11*18
SACL-0200-EISA-256C
160
200
0.256
50.3
300
215
280
170
135
11*18
SACL-0250-EISA-204C
200
250
0.204
67.7
360
215
375
190
135
13*26
SACL-0300-EISA-170C
250
300
0.17
71.2
360
215
375
190
135
13*26
SACL-0400-EISA-128C
E
355
400
0.128
98.8
430
270
410
240
175
14*28
SACL-0480-EISA-106C
450
480
0.106
103.5
430
270
410
240
175
14*28
SACL-0600-EISA-850D
560
600
0.085
116.1
430
270
410
240
175
14*28
SACL-0800-EISA-640D
710
800
0.064
149.7
430
285
520
240
190
14*28
SACL-1000-EISA-508D
F
900
1000
0.0508
179
480
315
540
200
190
14*28
SACL-1100-EISA-460D
1000
1100
0.046
232.7
480
340
660
200
210
14*28
SACL-1400-EISA-360D
1200
1400
0.036
248.5
480
370
660
200
210
14*28
System voltage: 3-AC690V, 50HZ, double-quadrant explosion-proof series frequency converter, Insulation level: H; Ceiling of reactor temperature rise≤70K-80K
Specifications and models
Figure No.
Power of 6 pluse rectifier(KW)
Rated current(A)
Inductance (mH)
Weight (KG)
Dimensions(mm)
W
D
H
W0
D0
A*B
FACL-0090-EISC-564C
D
75
90
0.564
30.1
260
170
265
140
110
9*18
FACL-0110-EISC-460C
90
110
0.46
33.5
260
195
265
140
110
9*18
FACL-0150-EISC-340C
110
150
0.34
44.3
300
200
280
170
110
11*18
FACL-0200-EISC-256C
160
200
0.256
54.4
300
215
280
170
135
11*18
FACL-0250-EISC-204C
200
250
0.204
71.9
360
220
375
190
135
13*26
FACL-0300-EISC-170C
250
300
0.17
77.9
360
220
375
190
135
13*26
FACL-0400-EISC-128C
E
355
400
0.128
106.6
430
280
410
240
175
14*28
FACL-0480-EISC-106C
450
480
0.106
117.8
430
280
410
240
175
14*28
FACL-0600-EISC-850D
560
600
0.085
135.9
430
280
410
240
175
14*28
FACL-0800-EISC-640D
710
800
0.064
162.8
430
310
510
240
190
14*28
FACL-1000-EISC-508D
F
900
1000
0.0508
190.6
480
310
540
200
190
14*28
FACL-1100-EISC-460D
1000
1100
0.046
229.4
480
345
660
200
210
14*28
FACL-1400-EISC-360D
1200
1400
0.036
252.5
480
365
660
200
210
14*28
System voltage: 3-AC1140V, 50HZ, double-quadrant explosion-proof series frequency converter, Insulation level: H; Ceiling of reactor temperature rise≤70K-80K
Specifications and models
Figure No.
Power of 6 pluse rectifier(KW)
Rated current(A)
Inductance (mH)
Weight (KG)
Dimensions(mm)
W
D
H
W0
D0
A*B
FACL-0110-EISC-760C
D
160
110
0.76
52.0
300
195
280
170
135
11*18
FACL-0150-EISC-560C
200
150
0.56
72.8
360
210
375
190
135
13*26
FACL-0200-EISC-420C
E
280
200
0.42
98.6
430
230
410
240
165
14*28
FACL-0250-EISC-336C
355
250
0.336
107.1
430
250
410
240
175
14*28
FACL-0300-EISC-280C
450
300
0.28
116.2
430
250
410
240
175
14*28
FACL-0350-EISC-240C
500
350
0.24
130.8
430
270
410
240
195
14*28
FACL-0400-EISC-210C
630
400
0.21
147.4
430
300
510
240
195
14*28
FACL-0480-EISC-175C
F
710
480
0.175
170.7
480
300
540
200
190
14*28
FACL-0600-EISC-140C
900
600
0.14
193.2
480
300
540
200
190
14*28
FACL-0700-EISC-120C
1000
700
0.12
239.5
480
330
660
200
210
14*28
FACL-0800-EISC-105C
1200
800
0.105
253.6
480
330
660
200
210
14*28
Remarks:Copper DC reactor(type EISC) will be a little heavier, the remaining items are the same, A/B/C stand for three-phase input side;X/Y/Z stand for output side.