Recommendation
Current position:Home > Photovoltaic Isolation Transformer > Isolation Transformer for PV Industry
Circuitry application:
Installed between the photovoltaic inverter and the power grid, its own leakage inductance works as L1, functioning with the filter reactor as a LCL wave filtering system.
Performance features:
System voltage |
3-AC270V/ AC300V/AC315V,50HZ |
Insulation grade |
F/H |
Noise |
≤50 d B |
Electric strength |
AC3000V 50Hz 5s leakage current≤5m A |
Temperature rise |
≤120℃ |
Ambient temperature |
-25℃~55℃ |
Operative norm |
GB 1094.11-2007 power transformer Part.11: Dry-type transformer |
Dimensions and technical parameter:
Technical parameter of transformer for PV industry in power station
Isolation transfromer for PV industry in power station. Temperature rise: 120K(level H), acquiescent connection: Dyn11, ratio-voltage: 0.27(0.3)(0.315)/0.38(0.4) |
||||||||||||
Models |
Figure No. |
Efficiency ≥ |
Rated power(KW) |
No-load current≤ |
Short-circuit impedance(±20%) |
Leakage inductance (m H)(±30%) |
Weight (Kg) |
Dimensions (mm) |
||||
W |
D |
H |
W0 |
D0 |
||||||||
SGL-100-EISA-0.315/0.4 |
/ |
98% |
100 |
4% |
4% |
0.48 |
439 |
600 |
515 |
620 |
300 |
335 |
SGL-125-EISA-0.315/0.4 |
98% |
125 |
4% |
4% |
0.48 |
492 |
630 |
515 |
620 |
320 |
335 |
|
SGL-250-EISA-0.315/0.4 |
98% |
250 |
3% |
4% |
0.2 |
754 |
750 |
565 |
800 |
400 |
335 |
|
SGL-500-EISA-0.315/0.4 |
98.5% |
500 |
3% |
4% |
0.1 |
1240 |
990 |
655 |
900 |
600 |
345 |
|
SGL-630-EISA-0.315/0.4 |
98.5% |
630 |
2% |
4% |
0.1 |
1472 |
1060 |
705 |
900 |
680 |
355 |